Technical Data of the Analog Outputs¶
Number of channels per module | 4, all channels for voltage and current | |
Distribution of channels into groups | 1 group of 4 channels | |
Channels O0-…O3- | Terminals 3.0…3.3 | |
Channels O0+…O3+ | Terminals 4.0…4.3 | |
Output type | bipolar with voltage, unipolar with current | |
Electrical isolation | against internal supply and other modules | |
Configurability | -10…+10 V, 0…20 mA, 4…20 mA (each output can be configured individually), current outputs only channels 0…3 | |
Output resistance (load), as current output |
0…500 W | |
Output loadability, as voltage output |
max. ±10 mA | |
Indication of the output signals | one LED per channel | |
Resolution | 12 bits (+ sign) | |
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range | typ. 0.5 %, max. 1 % For XC version below 0 °C and above 60 °C: on request |
|
Relationship between output signal and hex code | table Output ranges voltage and current Analog Input/Output Module AX521 | |
Unused outputs | can be left open-circuited |