Parameterization¶
The arrangement of the parameter data is depending on the firmware version installed inside the CPUs and Bus Modules:
Firmware version | Mounting position | Configuration |
---|---|---|
Firmware version < V2.0.0 |
|
The arrangement of the parameter data is performed by PLC-Configuration inside Control Builder software. |
|
The arrangement of the parameter data is performed by your master configuration software SYCON.net in connection with the S500 GSD files and in conjunction with the Control Builder software. | |
Firmware version > V2.0.0 |
|
The arrangement of the parameter data is performed by Control Builder Plus software. |
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configuration.
Module slot address: Y = 1…7
No. | Name | Value | Internal value |
Internal value, type |
Default | Min. | Max. | EDS Slot/Index |
---|---|---|---|---|---|---|---|---|
1 | Module ID | Internal | 1505 *1) |
Word | 1505 0x05dc |
0 | 65535 | 0x0Y01 |
2 *2) |
Ignore module | No Yes |
0 1 |
Byte | No 0x00 |
not for FBP | ||
3 | Parameter length in bytes | Internal | 21 | Byte | 21-CPU 21-FBP |
0 | 255 | 0x0Y02 |
4 | Check supply | Off On |
0 1 |
Byte | On 0x01 |
0 | 1 | 0x0Y03 |
5 | Analog data format | Default | 0 | Byte | Default 0x00 |
0x0Y04 | ||
6 | Behaviour of outputs at communication errors | Off Last value Substitute value |
0 1+(n*5) 2+(n*5), n <= 2 |
Byte | Off 0x00 |
0 | 2 | 0x0Y05 |
7 | Channel configuration Input channel 0 |
see table Channel configuration |
Byte | Default 0x00 |
0 | 19 | 0x0Y06 | |
8 | Channel monitoring Input channel 0 |
see table Channel monitoring |
Byte | Default 0x00 |
0 | 3 | 0x0Y07 | |
9 to 14 |
Channel configuration and channel monitoring of the input channels 1 to 3 | see tables channel configuration and channel monitoring |
Byte Byte |
Default 0x00 0x00 |
0 0 |
19 3 |
0x0Y08 to 0x0Y0D |
|
15 | Channel configuration Output channel 0 |
see table Channel configuration |
Byte | Default 0x00 |
0 | 130 | 0x0Y0E | |
16 | Channel monitoring Output channel 0 |
see table Channel monitoring |
Byte | Default 0x00 |
0 | 3 | 0x0Y0F | |
17 | Substitute value Output channel 0 |
only valid for output channel 0 | 0…0xffff | Word | Default 0x0000 |
0 | 65535 | 0x0Y10 |
18 to 21 | Channel configuration and channel monitoring of the output channels 1 to 2 | see tables channel configuration and channel monitoring |
Byte Byte |
Default 0x00 0x00 |
0 0 |
130 3 |
0x0Y11 to 0x0Y14 |
|
22 | Channel configuration Output channel 3 |
see table Channel configuration |
Byte | Default 0x00 |
0 | 130 | 0x0Y15 | |
23 | Channel monitoring Output channel 3 |
see table Channel monitoring |
Byte | Default 0x00 |
0 | 3 | 0x0Y16 |
*1) With CS31 and addresses less than 70 and FBP, the value is increased by 1
*2) Not with FBP
GSD file:
AX521 | Ext_User_Prm_Data_Len = Ext_User_Prm_Data_Const(0) = |
24 0x05, 0xe2, 0x15, \ 0x01, 0x00, 0x00 \ 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \ 0x00, 0x00, 0x00, 0x00, \ 0x00, 0x00, 0x00, 0x00, 0x00, 0x00; |
Input channel (4x):
No. | Name | Value | Internal value |
Internal value, type |
Default | Min. | Max. |
---|---|---|---|---|---|---|---|
1 | Channel configuration | see below *2) | see below *2) | Byte | 0 0x00 see below *3) |
||
2 | Channel monitoring | see below *4) | see below *4) | Byte | 0 0x00 see below *5) |
- Channel configuration
*2) | Internal value | Operating modes of the analog inputs, individually configurable |
---|---|---|
*3) | 0 | Unused (default) |
1 | Analog input 0…10 V | |
2 | Digital input | |
3 | Analog input 0…20 mA | |
4 | Analog input 4…20 mA | |
5 | Analog input -10 V…+10 V | |
8 | Analog input Pt100, -50 °C…+400 °C (2-wire) | |
9 | Analog input Pt100, -50 °C…+400 °C (3-wire), requires 2 channels *) | |
10 | Analog input 0…10 V via differential inputs, requires 2 channels *) | |
11 | Analog input -10 V…+10 V via differential inputs, requires 2 channels *) | |
14 | Analog input Pt100, -50 °C…+70 °C (2-wire) | |
15 | Analog input Pt100, -50 °C…+70 °C (3-wire), requires 2 channels *) | |
16 | Analog input Pt1000, -50 °C…+400 °C (2-wire) | |
17 | Analog input Pt1000, -50 °C…+400 °C (3-wire), requires 2 channels *) | |
18 | Analog input Ni1000, -50 °C…+150 °C (2-wire) | |
19 | Analog input Ni1000, -50 °C…+150 °C (3-wire), requires 2 channels *) | |
*) In the operating modes with 3-wire configuration or with differential inputs, two adjacent analog inputs belong together (e.g. the channels 0 and 1). In these cases, both channels are configured in the desired operating mode. The lower address must be the even address (channel 0). The next higher address must be the odd address (channel 1). The converted analog value is available at the higher address (channel 1). |
- Channel monitoring
*4) | Internal value | Monitoring |
---|---|---|
*5) | 0 | Plausibility, open-circuit (broken wire) and short-circuit |
3 | No monitoring |
Output channel 0 (1 channel):
No. | Name | Value | Internal value |
Internal value, type |
Default | Min. | Max. |
---|---|---|---|---|---|---|---|
1 | Channel configuration | see below *6) | see below *6) | Byte | see below *7) | ||
2 | Channel monitoring | see below *8) | see below *8) | Byte | see below *9) | ||
3 | Substitute value *10) |
0…65535 | 0… 0xffff |
Word | 0 |
Output channels 1…3 (3x):
No. | Name | Value | Internal value |
Internal value, type |
Default | Min. | Max. |
---|---|---|---|---|---|---|---|
1 | Channel configuration | see below *6) | see below *6) | Byte | see below *7) | ||
2 | Channel monitoring | see below *8) | see below *8) | Byte | see below *9) |
- Channel configuration
*6) | Internal value | Operating modes of the analog outputs, individually configurable |
---|---|---|
*7) | 0 | Unused (default) |
128 | Analog output -10 V…+10 V | |
129 | Analog output 0…20 mA (not with the channels 4…7 and 12…15) | |
130 | Analog output 4…20 mA (not with the channels 4…7 and 12…15) |
- Channel monitoring
*8) | Internal value | Monitoring |
---|---|---|
*9) | 0 | Plausibility, open-circuit (broken wire) and short-circuit (default) |
3 | No monitoring |
- Substitute value
*10) | Intended behaviour of output channel when the control system stops: | Required setting of the module parameter “Behaviour of outputs in case of a communication error” | Required setting of the channel parameter “Substitute value” |
---|---|---|---|
Output OFF | Off | 0 | |
Last value infinite | Last value | 0 | |
Last value for 5 s and then turn off | Last value 5 sec | 0 | |
Last value for 10 s and then turn off | Last value 10 sec | 0 | |
Substitute value infinite | Substitute value | depending on configuration | |
Substitute value for 5 s and then turn off | Substitute value 5 sec | depending on configuration | |
Substitute value for 10 s and then turn off | Substitute value 10 sec | depending on configuration |