Connection of analog output loads (voltage, current)¶
The following figure shows the connection of analog output loads (voltage, current).
1 analog load requires 1 channel
The following measuring ranges can be configured Analog Input/Output Module AX521 Analog Input/Output Module AX521 :
Voltage | -10 V…+10 V | Load max. ±10 mA | 1 channel used |
Current | 0…20 mA | Load 0…500 Ω | 1 channel used |
Current | 4…20 mA | Load 0…500 Ω | 1 channel used |
Only the channels 0…3 can be configured as current output (0…20 mA or 4…20 mA).
The function of the LEDs is described under Displays Analog Input/Output Module AX521.
Unused analog outputs can be left open-circuited.