Technical DataΒΆ
The System Data of AC500-eCo System Data AC500-eCo are valid here. Only additional details are therefore documented below.
| Process voltage UP | ||
| Connections | Terminals 17 and 19 for UP (+24 V DC); Terminals 18 and 20 for ZP (0 V) | |
| Rated value | 24 V DC | |
| Current consumption via UP terminal | 10 mA + 0.1 A per output (max.) | |
| Max. ripple | 5 % | |
| Inrush current | 0.000001 A s |
|
| Protection against reversed voltage | Yes | |
| Protection fuse on UP | Recommended; the outputs must be protected by an 1 A fast fuse | |
| Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/Bus Module | Ca. 10 mA | |
| Electrical Isolation | Yes, between the input/output group and the rest oft module | |
| Isolated groups | 1 group for 16 channels | |
| Surge voltage (max.) | 35 V DC for 0.5 s | |
| Max. power dissipation within the module | On request | |
| Weight | Ca. 115 g | |
| Mounting position | Horizontal or vertical | |
| Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. | |