Diagnosis

E1..E4 d1 d2 d3 d4

Identifier

000..063

AC500-Display <−  Display in
Class Comp Dev Mod Ch Err PS501 PLC Browser

Byte 6

Bit 6..7

- Byte 3 Byte 4 Byte 5

Byte 6

Bit 0..5

PNIO diagnosis block
Class Interface Device Module Channel Error Identifier Error message Remedy
 
     
Module error DO571
3 14 1..10 31 31 19 Checksum error in the I/O module Replace I/O Module
11 / 12 ADR 1..10
3 14 1..10 31 31 43 Internal error in the module Replace I/O Module
11 / 12 ADR 1..10
3 14 1..10 31 31 9 Overflow diagnosis buffer Restart
11 / 12 ADR 1..10
4 14 1..10 31 31 26 Parameter error Check master
11 / 12 ADR 1..10
3 14 1..10 31 31 11 Process voltage too low Check process voltage
11 / 12 ADR 1..10

Remarks:

In AC500 the following interface identifier applies:

14 = I/O-Bus, 11 = COM1 (e.g. CS31-Bus), 12 = COM2.

The PNIO diagnosis block does not contain this identifier.

With “Device” the following allocation applies:

31 = Module itself, 1..10 = Expansion module 1..10, ADR = Hardware address (e. g. of the DC551-CS31)

With “Module” the following allocation applies dependent of the master:

Module error: I/O-Bus or PNIO: 31 = Module itself; COM1/COM2: 1..10 = expansion 1..10

Channel error: I/O-Bus or PNIO = Module type (2 = DO); COM1/COM2: 1..10 = expansion 1..10

In case of module errors, with channel “31 = Module itself” is output.