Technical DataΒΆ
The System Data of AC500-eCo System Data AC500-eCo are valid here. Only additional details are therefore documented below.
Process supply voltage L+ | |
Connections | Terminal 20 for L+ (+24 V DC). The minus pole is provided by the I/O-Bus. |
Rated value | 24 V DC |
Current consumption via L+ | 50 mA |
Max. ripple | 5 % |
Protection against reversed voltage | Yes |
Rated protection fuse for UP | Recommended; the outputs must be protected by an 3 A fast fuse |
Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/Bus Module | Ca. 5 mA |
Electrical isolation | Yes, between the output groups and the rest oft module |
Isolated groups | 2 (4 channels per group) |
Surge-voltage (max.) | 35 V DC for 0.5 s |
Max. power dissipation within the module | 2.0 W |
Weight | Ca. 150 g |
Mounting position | Horizontal or vertical |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |