Parameters of the Module

Name Value

Internal

Value

Internal

Value, type

Default
Module ID *1) Internal 0x1C84 WORD 0x1C84
Parameter length Internal 54 BYTE 54
Error LED / Failsafe function (table errorLED / Failsafe function CANopenâ Bus Module CI581-CN) On 0 BYTE 0
Off by E4 1
Off by E3 2
On + failsafe 16
Off by E4 + failsafe 17
Off by E3 + failsafe 18
Reserved 0 0 ARRAY of 24 BYTES  
Check supply (UP and UP3) On 0 BYTE  
Off 1 1
Fast counter 0 0 BYTE 0
: :  
10 *2) 10  

*1) With a faulty ID, the Modules reports a “parameter error” and does not perform cyclic process data transmission

*2) Counter operating modes, see description of the Fast Counter.

Table Settings “errorLED / Failsafe function”

Setting Meaning
On Error-LED (S-ERR) lights up at errors of all error classes, Failsafe-mode off
Off by E4 Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3, Failsafe-mode off
Off by E3 Error LED (S-ERR) lights up at errors of error classes E1 and E2, Failsafe-mode off
On +Failsafe Error-LED (S-ERR) lights up at errors of all error classes, Failsafe-mode on*
Off by E4 + Failsafe Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3, Failsafe-mode on*
Off by E3 + Failsafe Error LED (S-ERR) lights up at errors of error classes E1 and E2, Failsafe-mode on*
* The parameters Behaviour analog outputs at communication error and Behaviour digital outputs at communication error are only evaluated if failsafe function is enabled.