Substitute value

Table Substitute value

Intended behaviour of output channel  when the control system stops: Required setting of the module parameter “Behaviour of outputs in case of a communication error” Required setting of the channel parameter “Substitute value”
Output OFF Off 0
Last value infinite Last value 0
Last value for 5 s and then turn off Last value 5 sec 0
Last value for 10 s and then turn off Last value 10 sec 0
Substitute value infinite Substitute value depending on configuration
Substitute value for 5 s and then turn off Substitute value 5 sec depending on configuration
Substitute value for 10 s and then turn off Substitute value 10 sec depending on configuration