Connection of passive-type analog sensors (current) to the analog inputs

The following figure shows the connection of passive-type analog sensors (current) to the analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.

../_images/9cf580316196bf340a33139073f3a0c81

Connection of passive-type analog sensors (current) to the analog inputs

The following measuring ranges can be configured CANopenâ Bus Module CI581-CN CANopenâ Bus Module CI581-CN :

Current 4…20 mA 1 channel used

The function of the LEDs is described under Diagnosis and displays / Displays.

Caution

:strong:Risk of overloading the analog input!

If an analog current sensor supplies more than 25 mA for more than 1 second during initialization, this input is switched off by the module (input protection).

Use only sensors with fast initialization or without current peaks higher than 25 mA. If not possible, connect a 10-volt zener diode in parallel to I+ and I-.

Unused input channels can be left open-circuited, because they are of low resistance.