Operating and Ambient Conditions¶
Voltages, according to EN 61131-2 | ||
---|---|---|
24 V DC | Process and supply voltage | 24 V DC (-15 %, +20 % without ripple) |
Absolute limits | 19.2 V…30 V inclusive ripple | |
Ripple | < 5 % | |
Protection against reverse polarity | 10 s | |
120 V AC | Line voltage | 120 V AC (-15 %, +10 %) |
Frequency | 47 Hz..62.4 Hz / 50…60 Hz (-6 %, +4 %) | |
230 V AC | Line voltage | 230 V AC (-15 %, +10 %) |
Frequency | 47 Hz..62.4 Hz / 50…60 Hz (-6 %, +4 %) | |
120-240 V AC | Wide-range supply | |
Line voltage | 102 V…264 V / 120 V…240 V (-15 %, +10 %) | |
Frequency | 47 Hz..62.4 Hz / 50…60 Hz (-6 %, +4 %) | |
Allowed interruptions of power supply, according to EN 61131-2 | ||
DC supply | Interruption < 10 ms, time between 2 interruptions > 1 s, PS2 | |
AC supply | Interruption < 0.5 periods, time between 2 interruptions > 1 s |
Attention
Important: Exceeding the maximum power supply voltage (>30 V DC) for process or supply voltages could lead to unrecoverable damage of the system. The system could be destroyed.
Temperature | ||
---|---|---|
Operating | 0 °C…+60 °C (horizontal mounting of modules) 0 °C…+40 °C (vertical mounting of modules and output load reduced to 50 % per group) |
|
Storage | -40 °C…+70 °C | |
Transport | -40 °C…+70 °C | |
Humidity | Max. 95 %, without condensation | |
Air pressure | ||
Operating | > 800 hPa / < 2000 m | |
Storage | > 660 hPa / < 3500 m |