Electromagnetic CompatibilityΒΆ
| Immunity | |
|---|---|
| Against electrostatic discharge (ESD) | According to EN 61000-4-2, zone B, criterion B |
| Electrostatic voltage in case of air discharge | 8 kV |
| Electrostatic voltage in case of contact discharge | 4 kV, in a closed switch-gear cabinet 6 kV 1) |
| ESD with communication connectors | In order to prevent operating malfunctions, it is recommended, that the operating personnel discharge themselves prior to touching communication connectors or perform other suitable measures to reduce effects of electrostatic discharges. |
| ESD with connectors of Terminal Bases | The connectors between the Terminal Bases and CPUs or Communication Modules must not be touched during operation. The same is valid for the I/O-Bus with all modules involved. |
| Immunity | |
| Against the influence of radiated (CW radiated) | According to EN 61000-4-3, zone B, criterion A |
| Test field strength | 10 V/m |
| Immunity | |
| Against transient interference voltages (burst) | According to EN 61000-4-4, zone B, criterion B |
| Supply voltage units (AC, DC) | 2 kV |
| Digital inputs/outputs (24 V DC) | 2 kV |
| Digital inputs/outputs (120/230 V AC) | 2 kV |
| Analog inputs/outputs | 1 kV |
| CS31 system bus | 2 kV |
| Serial RS-485 interfaces (COM) | 2 kV |
| Serial RS-232 interfaces (COM, not for PM55x and PM56x) | 1 kV |
| ARCNET | 1 kV |
| FBP | 1 kV |
| Ethernet | 1 kV |
| I/O supply, DC-out | 1 kV |
| Immunity | |
| Against the influence of line-conducted interferences (CW conducted) | According to EN 61000-4-6, zone B, criterion A |
| Test voltage | 3V zone B, 10 V is also met. |
| High energy surges | According to EN 61000-4-5, zone B, criterion B |
| Power supply AC | 2 kV CM* / 1 kV DM* |
| Power supply DC | 1 kV CM* / 0.5 kV DM* |
| DC I/O supply, add. DC-supply-out | 0.5 kV CM* / 0.5 kV DM* |
| Buses, shielded | 1 kV CM* |
| AC-I/O unshielded | 2 kV CM* / 1 kV DM* |
| I/O analog, I/O DC unshielded | 1 kV CM* / 0.5 kV DM* |
| * CM = Common Mode, * DM = Differential Mode | |
| Radiation (radio disturbance) | According to EN 55011, group 1, class A |
1) High requirement for shipping classes are achieved with additional specific measures (see specific documentation).