Configuration of the Extended Settings PM5xy-ETH Onboard Ethernet < \ CBP 2.4

Tab Extended settings provides settings for the extended features of the PM5xy-ETH onboard Ethernet, such as SNTP or the web server:

../_images/dc14590f45ff83f10a33139000eba54e

The following parameters are available:

Parameter Default Value Meaning Parameter
Remote configuration
ABB NetConfig protocol active Enabled Disabled ABB NetConfig protocol is disabled. -
Enabled ABB NetConfig protocol is enabled.
SNTP configuration
SNTP protocol active Disabled Disabled SNTP protocol is inactive. -
Enabled SNTP protocol is active.
Client
Client mode active Disabled Disabled SNTP client mode is disabled. -
Enabled SNTP client mode is enabled.
Server 0.0.0.0 Valid IP address IP address of the SNTP server. -
Backup server 0.0.0.0 Valid IP address IP address of the SNTP server which will be used if the primary server is unreachable. -
Interval 60 15…120 Parameter Interval sets the interval in [s] for outgoing SNTP requests. -
Wait for sync before RUN   Disabled CPU does not wait for time synchronization from SNTP server and turns to RUN state immediately. -
Enabled CPU waits for time synchronization from SNTP server and remains in Stop state after the time is over.
Time to wait for sync 10 1…120 The time the CPU waits for receiving the time synchronization from SNTP server. If the CPU does not receive a valid time within the given period, an EC4 error appears. -
Allow timejumps Disabled Disabled Timejumps lead to an EC4 error in the CPU. -
Enabled Timejumps are accepted. Parameter Allowed threshold for timejumps can be adapted to determine the threshold for the timejumps. If the needed timejump exceeds the threshold, the CPU refuses the setting of time received from SNTP server and an EC4 error appears.
Allowed threshold for timejumps 60 1…3600 Parameter Allowed threshold for timejumps represents the threshold which is allowed for timejumps in [s]. -
Server
Server mode active Disabled Disabled SNTP server is disabled. -
Enabled SNTP server is enabled.
Access control 0.0.0.0/24 Valid IP address

Parameter Access control sets the subnet from which incoming SNTP requests are accepted. Request from other subnets will be ignored.

Here you can enter 0.0.0.0/24

That means the IP address/ Subnet mask

The subnetmask 24 means 255.255.255.0

The subnetmask 16 means 255.255.0.0

-
Web server (see section Configuration of the Web server for more information)
Web server active Disabled Disabled Web server is disabled and not available. Web server active
Enabled Web server is enabled and available.
Port 80 0…65535 Listen port of the web server. Port
Connections 1 1…25 (depending on CPU type) Number of parallel connections accepted by the web server. Connections