RCOM_COLDST

../_images/8986c7aee38af27f0a33139000eba54e
Parameter Value
Library_File_Name RCOM_AC500_V13.lib
Firmware V1.3.1
Type Type_Function_Block_History
Group RCOM/RCOM+ communication

This Function Block performs a cold start of the called slave(s). After the cold start, the slave(s) are partially reinitialized.

At the called slave(s) the sequence marks (RCOM-specific protocol parameter) are reset and the transmission of data records is disabled. All entries in the event queue are deleted, and, after this, a cold start event is generated.

After a cold start, always a normalization is required.

This Function Block has to be used for the initialization of the RCOM network, e.g. after the initialization of the master’s CM574-RCOM device.