Parameterization of the Onboard I/O for PM564

The 2 analog onboard inputs can be configured as 2 digital onboard inputs, so the maximal digital inputs number is 8. The input and output channels can be provided as WORD, BYTE and BOOL.

Double-click on I/O (onboard IOs) to open the DI+6DO+2AI+1AO configuration in the editor window:

../_images/94038b0545ff011c0a33139000eba54e1

The 6DI+6DO+2AI+1AO onboard I/Os support the following channel functions:

Onboard I/O Type Channel Function Max. Number Channel Name
Digital onboard I/O Digital Input 8

Digital input channel 0..5

Analog input channel AI0..AI1 *

Fast counter 2 Input channel 0, 1
Interrupt input 4 Input channel 0..3
Digital output 5 Output channel 0..5
PWM output 2 Output channel 2..3
Analog onboard I/O Analog input 2 Input channel AI0..AI1 *
Analog output 1 Output channel AO0

* These 2 analog inputs can be configured as 2 digital inputs

Same as PM554, the Processor Module PM564 has a maximum of 8 digital onboard inputs and 6 digital onboard outputs. The channel parameters for onboard digital I/Os are the same as those of PM554 and can be found in table onboard I/Os for PM554 Parameterization of the Onboard I/Os for PM55x-xP. Analog input channels AI0&AI1 on PM564 are for digital input channels 5&7 on PM554.

PM564: Channel parameters for onboard analog I/Os
Onboard I/O Type Parameter Channel Name Default Value Value Meaning
Analog inputs Input delay digital input Channel AI0&A1 8 ms 0.1 ms Configure 0.1 ms input delay
1 ms Configure 1 ms input delay
8 ms Configure 8 ms input delay
32 ms Configure 32 ms input delay
Channel configuration Digital input Digital input Configure the channel as normal digital input
Analog input 0..10 V Configure the channel as 0..10 V analog input
Analog outputs Channel configuration Channel AO0 Analog output 0..10 V Analog output 0..10 V Configure the channel as 0..10 V analog output
Analog output 0..20mA Configure the channel as 0..20 mA analog output
Analog output 4..20 mA Configure the channel as 4..20 mA analog output

Note

Default value of channel AI0&AI1 is digital input. The user has to change the configuration parameter to enable the analog input function.