Checking the CS31 ModulesΒΆ
Double-click on COMx_CS31_Bus (COMx - CS31-Bus) and select the tab Check CS31 modules to open the following overview to check the CS31 Bus Configuration concerning the attached modules:
The following information is show in the view:
Parameter | Meaning |
---|---|
Number of CS31 modules | The current number of configured CS31 Modules at the CS31 Master. It is not allowed to attach more than 31 slave devices to the bus. |
CS31 Cycletime | The predicted CS31 cycle time in [ms]. The value may not exceed 75 ms. |
The following image shows an example of the error message that appears in case of a violation of the described parameters:
The icon indicates the parameter that was violated.
Note
The violation message does not block the download of an invalid configuration.