Technical Data

The System Data of AC500 and S500 System Data AC500 are valid here. Only additional details are therefore documented below.

Communication Module CM574-RS  
Protocol Programmable with Automation_Builder e.g. Modbus / ASCII via serial interfaces
Interface Serial interface
Serial interface standard EIA RS-232 or EIA RS-485
Potential separation Yes, from the CPU, 500 V DC
Serial interface parameters Configurable via software
Modes of operation Programming or data exchange
Transmission rate 9.6 kBit/s to 187.5 kBit/s
Protocol Programmable
Interface connector MC 0.5/9-G-2.5, 9-pole, male
Processor PowerPC
Usable CPUs PM57x, PM58x, PM59x PM57x (-y), PM58x (-y) and PM59x (-y)
Usable Terminal Bases All TB5xx TB51x-TB54x
Ambient temperature 0 °C…60 °C
Communication Module Bus Dual-port memory, 8 kByte
Internal power supply Through the Communication Module Bus of the Terminal Base
Current consumption from 24 V DC power supply at the Terminal Base of the CPU Typ. 80 mA
Internal RAM memory 256 kByte
External RAM memory -
External Flash memory 512 kByte (firmware) + 2 x 64 kByte (user data)
Status display PWR, RDY, RUN, STA, ERR
Weight Ca. 150 g