Parameterization

The arrangement of the parameter data is depending on the firmware version installed inside the CPUs and Bus Modules:

Firmware version Mounting position Configuration
Firmware version < V2.0.0
  • I/O Module connected locally to a CPU
  • I/O Module connected to CS31 Bus Module
The arrangement of the parameter data is performed by PLC-Configuration inside Control Builder software.
  • I/O Module connected remotely to a Bus Module (not CS31)
The arrangement of the parameter data is performed by your master configuration software SYCON.net in connection with the S500 GSD files and in conjunction with the Control Builder software.
Firmware version > V2.0.0
  • All
The arrangement of the parameter data is performed by Control Builder Plus software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module AO523: Module slot address: Y = 1…7

No. Name Value

Internal

value

Internal

value, type

Default Min. Max.

EDS

Slot/Index

1 Module ID Internal

1510

*1)

Word

1510

0x05e6

0 65535 0x0Y01

2

*2)

Ignore module

No

Yes

0

1

Byte

No

0x00

    not for FBP
3 Parameter length in bytes Internal 39 Byte

39-CPU

39-FBP

0 255 0x0Y02
4 Check supply

Off

On

0

1

Byte

On

0x01

0 1 0x0Y03
5 Analog data format Default 0 Byte

Default

0x00

    0x0Y04
6 Behaviour of outputs at communication errors

Off

Last value

Substitute value

0

1+(n*5)

2+(n*5),

n <= 2

Byte

Off

0x00

0 2 0x0Y05
7

Channel configura tion

Output channel 0

see table

Channel configuration

Byte

Default

0x00

0 130 0x0Y06
8

Channel monitori ng

Output channel 0

see table

Channel monitoring

Byte

Default

0x00

0 3 0x0Y07
9

Substitute value

Output channel 0

Output channel 0! 0…0xffff Word

Default

0x0000

0 65535 0x0Y08
10 to 15 Channel configuration and channel monitoring of the output channels 1 to 3

see tables

channel configuration and channel monitoring

Byte

Byte

Default

0x00

0x00

0

0

130

3

0x0Y09

to

0x0Y0E

16 to 23 Channel configuration and channel monitoring of the output channels 4 to 7

see tables

channel configuration and channel monitoring

Byte

Byte

Default

0x00

0x00

0

0

128

3

0x0Y0F

to

0x0Y16

24

Channel configura tion

Output channel 8

see table

Channel configuration

Byte

Default

0x00

0 130 0x0Y17
25

Channel monitorin g

Output channel 8

see table

Channel monitoring

Byte

Default

0x00

0 3 0x0Y18
26

Substitute value

Output channel 8

Output channel 8! 0…0xffff Word

Default

0x0000

0 65535 0x0Y19

27

to

32

Channel configuration and channel monitoring of the output channels 9 to 11

see tables

channel configuration and channel monitoring

Byte

Byte

Default

0x00

0x00

0

0

130

3

0x0Y1A

to

0x0Y1F

33

to

40

Channel configuration and channel monitoring of the output channels 12 to 15

see tables

channel configuration and channel monitoring

Byte

Byte

Default

0x00

0x00

0

0

128

3

0x0Y20

to

0x0Y27

*1) With CS31 and addresses less than 70 and FBP, the value is increased by 1

*2) Not with FBP

GSD file:

AO523

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const(0) =

42

0x05, 0xe7, 0x27, \

0x01, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00;

Output channels 0 and 8 (2 channels, AO523):

No. Name Value

Internal

value

Internal

value, type

Default Min. Max.
1 Channel configuration see below *6) see below *6) Byte see below *7)    
2 Channel monitoring see below *8) see below *8) Byte see below *9)    
3

Substitute value

*10)

0…65535

0…

0xffff

Word 0    

Output channels 1…7 and 9…15 (14 channels, AO523):

No. Name Value

Internal

value

Internal

value, type

Default Min. Max.
1 Channel configuration see below *6) see below *6) Byte see below *7)    
2 Channel monitoring see below *8) see below *8) Byte see below *9)    

- Channel configuration

*6) Internal value Operating modes of the analog outputs, individually configurable
*7) 0 Unused (default)
  128 Analog output -10 V…+10 V
  129 Analog output 0…20 mA (not with the channels 4…7 and 12…15)
  130 Analog output 4…20 mA (not with the channels 4…7 and 12…15)

- Channel monitoring

*8) Internal value Monitoring
*9) 0 Plausibility, open-circuit (broken wire) and short-circuit (default)
  1 Open-circuit (broken wire) and short-circuit
  2 Plausibility
  3 No monitoring

- Substitute value

*10) Intended behaviour of channel 0 when the control system stops: Required setting of the module parameter “Behaviour of outputs in case of a communication error” Required setting of the channel parameter “Substitute value”
  Output OFF OFF 0
  Last value Last value 0
  Substitute value OFF or Last value 1…65535