Input Description

../_images/33a7f81de389dfab0a33139000eba54e

EN (enable)

Data_Type Default_Value Range Unit
BOOL - - -

Input EN has to be continuously set to TRUE.

When the function block is called for the first time, input SLOT is checked for validity and the corresponding device is checked for correct configuration in the operating mode “IO mode”. If this is not the case, processing is aborted and an error is displayed. The function block outputs are updated as long as input EN = TRUE.

SLOT

Data_Type Default_Value Range Unit
BYTE - - -

This input is used to select the slot (module number) of the DC541.

The slots are numbered consecutively from right to left. Slot 1 is the first slot on the left of the CPU.

CH (channel)

Data_Type Default_Value Range Unit
BYTE - - -

Input is used to select the output to be pulsed.

PULSE

Data_Type Default_Value Range Unit
BYTE - - -

Input is used to specify the ratio for the TRUE signal (on time ratio).

PAUSE

Data_Type Default_Value Range Unit
BYTE - - -

Input is used to specify the ratio for the FALSE signal (off time ratio).

CYCLE

Data_Type Default_Value Range Unit
WORD - - µs

Input CYCLE is used to specify the minimum switching time of the output. The output remains in the TRUE or FALSE state for at least the time specified at CYCLE.

The minimum time specified at input CYCLE must not be smaller than the cycle time of the device DC541. Depending on its configuration, the cycle time of the DC541 can be 50, 100 or 200 µs. The cycle time can be polled using the Function Block DC541_GET_CFG, output CYCLE DC541_GET_CFG.