Interfaces for Inputs and OutputsΒΆ

PM57x, PM58x and\ PM59x (AC500)

The following input and output interfaces are available for the AC500 CPUs PM57x, PM58x and PM59x:

No. Type Designation Number of Inputs and Outputs
1 I/O bus Interface for I/O modules Max. 10 modules with a maximum of 32 channels (IX, QX, IW, QW) per module
2 COM1 CS31 bus master Max. 31 modules with a maximum of 32 channels per module, address 0-61
Decentralized I/O expansion RS-232 / RS-485 (version V2.0 and later)
3 COM2 Decentralized I/O expansion RS-232 / RS-485 (version V2.0 and later)
4 FBP FieldBusPlug - Slave Max. 8 modules with 16 IW + 16 QW + 16 IB + 16 QB with modular FBP, depending on fieldbus
5 Int. Communication Module Internal Communication Module ARCNET,.. (configuration without SYCON.net)
6 Line 0 Internal Communication Module 4 kB %I0.xx / %Q0.xx each
7 Line 1 Communication Module 1 4 kB %I1.xx / %Q1.xx each
8 Line 2 Communication Module 2 4 kB %I2.xx / %Q2.xx each
9 Line 3 Communication Module 3 4 kB %I3.xx / %Q3.xx each
10 Line 4 Communication Module 4 4 kB %I04.xx / %Q4.xx each

PM55x and PM56x (AC500-eCo)

The following inputs and outputs interfaces are available for the AC500-eCo CPUs PM55x and PM56x:

No. Type Designation Number of Inputs and Outputs
1 Onboard I/Os Onboard I/Os

Per module:

Option 1: 8DI+6DO

Option 2: 8DI+6DO+2AI+1AO

2 I/O-Bus Interface for I/O Modules Max. 7 I/O Modules with a maximum of 32 channels (IX, QX, IW, QW) per module
3 COM1 CS31 bus master Max. 31 modules with a maximum of 32 channels per module, address 0-61
Decentralized I/O expansion RS-485 (version V2.0 and later)
4 COM2 Decentralized I/O expansion RS-485 (version V2.0 and later)