Parameterization

The arrangement of the parameter data is performed with Control Builder Plus software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Name Value

Internal

Value

Internal

value, Type

Default Min. Max. EDS Slot Index
Module ID Intern 6505 *1) WORD 0x1969 0 65535 xx01
Ignore module

No

Yes

0

1

BYTE

No

0x00

     
Parameter length Intern 4 BYTE 0 0 255 xx02 *2)
Check Supply

Off

On

0

1

BYTE

On

0x01

     
Analog Data Format Default 0 BYTE

Default

0x00

  255  

*1) with CS31 and addresses less than 70, the value is increased by 1

*2) Value is hexadecimal: HighByte is slot (xx: 0 … 7), LowByte is index (1 … n)

GSD file:

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const(0) =

0x07

0x6A, 0x19, 0x04, \

0x01, 0x00, \

0x00, 0x00;