Technical Data of the Analog Inputs¶
Number of channels per module | 4 individually configurable voltage or current inputs | ||
Distribution of channels into groups | 1 (4 channels per group) | ||
Resolution | |||
Unipolar | Voltage: 0 V … +5 V; 0 V … + 10 V: 12 bits Current 0 mA … 20 mA; 4 mA … 20 mA: 12 bits |
||
Bipolar | Voltage -2.5 V … +2.5 V; -5 V … +5 V: 11 bits plus sign | ||
Connection of the signals I0- to I3- | Terminals 3, 6, 9, 12 | ||
Connection of the signals I0+ to I3+ | Terminals 2, 5, 8, 11 | ||
Input type | Differential | ||
Electrical isolation | No electrical isolation between the inputs and the I/O-Bus | ||
Common mode input range | Signal voltage plus common mode voltage must be within ±12 V | ||
Indication of the input signals | No | ||
Channel input resistance | Voltage: >1 MΩ, current: ca. 250 Ω | ||
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range | Typ. | 0.5 % of full scale (voltage) 0.5 % of full scale (current 0…20 mA) 0.7 % of full scale (current 4…20 mA) at 25°C |
|
Max. | 2 % of full scale (all ranges) at 0…60 °C or EMC disturbance |
||
Time constant of the input filter | Voltage: 300 µs, current: 300 µs | ||
Relationship between input signal and hex code | Table Measuring Ranges Analog Input Module AI561 | ||
Analog to digital conversion time | Typ. 500 µs per channel | ||
Unused inputs | Can be left open and should be configured as “unused” | ||
Overvoltage protection | Yes, up to 30 V DC only for voltage input | ||
Max. cable length (conductor cross section > 0,14 mm²) | |||
Unshielded wire | 10 m | ||
Shielded wire | 100 m |