OverviewΒΆ
The processor module can be operated manually using the function keys on the front panel:
Function Key | Description | Description |
---|---|---|
Run | Toggles between RUN and STOP mode. Switching into RUN mode is only possible if an error free project has been created and downloaded withAutomation_Builder. | |
Value | Shows different state values of the processor module. | |
Escape | Quits the current menu, submenu or function without saving. | |
OK / Acknowledgement | Acknowledges the current value or selects a menu/submenu. Changes that have been sent to the processor module successfully are confirmed with Done on the display. | |
Diagnostic | Currently no function. | |
Configuration | Show/set IP configuration, PLC startup mode and ETHERNET address. | |
Count up | Press the function key repeatedly in order to increase the value each time by 1. Keep the function key pressed in order to count up fast. | |
Count down | Press the function key repeatedly in order to decrease the value each time by 1. Keep the function key pressed in order to count down fast. |
Backlight is switched on for about 20 seconds by pressing any function key.