Short Description of the CI521-MODTCP ParametersΒΆ
| Parameter | Single parameter index | Description | Additional Info | 
|---|---|---|---|
| 0 | Module ID (high Byte) | Fixed, must be 16#1C | |
| 1 | Module ID (low Byte) | Fixed, must be 16#E8 | |
| 2 | Ignore Module | Reserved, must be 0 | |
| 3 | Length of following parameter block | Fixed, must be 16#3F | |
| 4 | 0 | Error LED / Failsafe | See hardware description: AC500 Device Description (Hardware) | 
| 5 | 1 | Master IP Byte 0 | IP Address for write restrictions ( MODBUS Communication Interface Module) | 
| 6 | Master IP Byte 1 | ||
| 7 | Master IP Byte 2 | ||
| 8 | Master IP Byte 3 | ||
| 9 | 2 | Master IP 1 Byte 0 | IP Address for write restrictions ( MODBUS Communication Interface Module) | 
| 10 | Master IP 1 Byte 1 | ||
| 11 | Master IP 1 Byte 2 | ||
| 12 | Master IP 1 Byte 3 | ||
| 13 | 3 | Master IP 2 Byte 0 | IP Address for write restrictions ( MODBUS Communication Interface Module) | 
| 14 | Master IP 2 Byte 1 | ||
| 15 | Master IP 2 Byte 2 | ||
| 16 | Master IP 2 Byte 3 | ||
| 17 | 4 | Master IP 3 Byte 0 | IP Address for write restrictions ( MODBUS Communication Interface Module) | 
| 18 | Master IP 3 Byte 1 | ||
| 19 | Master IP 3 Byte 2 | ||
| 20 | Master IP 3 Byte 3 | ||
| 21 | 5 | Master IP 4 Byte 0 | IP Address for write restrictions ( MODBUS Communication Interface Module) | 
| 22 | Master IP 4 Byte 1 | ||
| 23 | Master IP 4 Byte 2 | ||
| 24 | Master IP 4 Byte 3 | ||
| 25 | 6 | Master IP 5 Byte 0 | IP Address for write restrictions ( MODBUS Communication Interface Module) | 
| 26 | Master IP 5 Byte 1 | ||
| 27 | Master IP 5 Byte 2 | ||
| 28 | Master IP 5 Byte 3 | ||
| 29 | 7 | Master IP 6 Byte 0 | IP Address for write restrictions ( MODBUS Communication Interface Module) | 
| 30 | Master IP 6 Byte 1 | ||
| 31 | Master IP 6 Byte 2 | ||
| 32 | Master IP 6 Byte 3 | ||
| 33 | 8 | Master IP 7 Byte 0 | IP Address for write restrictions ( MODBUS Communication Interface Module) | 
| 34 | Master IP 7 Byte 1 | ||
| 36 | Master IP 7 Byte 2 | ||
| 36 | Master IP 7 Byte 3 | ||
| 37 | 9 | Timeout | Timeout for bus supervision in 10ms steps if set to 0 no bus supervision is active  | 
| 38 | 10 (read only) | I/O Mapping Structure | See hardware description: AC500 Device Description (Hardware) | 
| 39 | 11 | Reserved | Reserved, must be 0 | 
| 40 | 12 | Reserved | Reserved, must be 0 | 
| 41 | 13 | Reserved | Reserved, must be 0 | 
| 42 | 14 | Check supply | See hardware description: AC500 Device Description (Hardware) | 
| 43 | 15 | Analogue data format | Reserved, must be 0 | 
| 44 | 16 | Input delay | See hardware description: AC500 Device Description (Hardware) | 
| 46 | 17 | Fast counter | |
| 46 | 18 | Short circuit detection | |
| 47 | 19 | Behavior binary outputs at com. fault | |
| 48 | 20 | Substitute value binary outputs | |
| 49 | 21 | Overvoltage monitoring | |
| 50 | 22 | Behavior analogue outputs | |
| 51 | 23 | Channel Config AI0 | |
| 52 | 24 | Check Channel AI0 | |
| 53 | 25 | Channel Config AI1 | |
| 54 | 26 | Check Channel AI1 | |
| 55 | 27 | Channel Config AI2 | |
| 56 | 28 | Check Channel AI2 | |
| 57 | 29 | Channel Config AI3 | |
| 58 | 30 | Check Channel AI3 | |
| 59 | 31 | Channel Config AO0 | |
| 60 | 32 | Check Channel AO0 | |
| 61 | 33 | Substitute value AO0 (high Byte) | |
| 62 | Substitute value AO0 (low Byte) | ||
| 63 | 34 | Channel Config AO1 | |
| 64 | 35 | Check Channel AO1 | |
| 65 | 36 | Substitute value AO1 (high Byte) | |
| 66 | Substitute value AO1 (low Byte) |