AC500 Battery

The AC500 battery buffers the following data in case of “control voltage off”:

Note

To prevent data loss when using the AC500 battery, the battery status should be periodically monitored by the user program.

Battery status

The battery status can be monitored either with the help of a user program on the PLC or in Automation_Builder.

In the PLC shell of Automation_Builder the command “batt” PLC Shell Commands”batt”: PLC Shell Commands

0 Battery empty
20 Remaining battery charge below 20 %
100 Battery charge OK

In the user program, the battery status can be checked with the function BATT which is available in the folder “Battery” of the system library ABB_ExtUtils_AC500.lib (Library Manager ‣ ABB-AC500 ‣ Use Cases). The following is output:

0 Battery empty
20 Remaining battery charge below 20 %, battery must be replaced
100 Battery charge OK

On the device, the battery status can be checked with the function keys of a Processor Module. LEDs, Display and Function Keys on the Front Panel

Reading out Values: Reading out Values