Online Access

Preferred driver for online access: 3S UDP block driver BlkDrvUdp. This driver allows to scan and select the connected PLC’s.

Alternative: 3S TCP/IP block driver. This driver requires at least 2 sockets:

  • 1x driver “BlkDrvTcp” on port 11740
  • 1x listen on port 11740 if PLC has established online connection

Note

Online access can be established from:

  • Automation_BuilderCommand ‘Login’: Menu ‘Online’
  • IEC 61131-3 editor OPC DA server
  • Panel CP600 series

Each established connection needs one socket. In addition one socket on port 11740 is listening.

  1. Startup the PLC.

    ⇒

    One socket on port 11740 (listen).

  2. Login from Automation_Builder via driver “BlKDrvTcp”.

    ⇒

    2 sockets on port 11740 (1x online, 1x listen)

  3. Additional login out of OPC server with the same driver.

    ⇒

    3 sockets on port 11740 (2x online, 1x listen)

  4. Additional connect CP600 via driver “BlkDrvTcp”.

    ⇒

    4 sockets on port 11740 (3x online, 1x listen)