Online Access

Preferred driver for online access: 3S UDP block driver BlkDrvUdp. This driver allows to scan and select the connected PLC’s.

Alternative: 3S TCP/IP block driver. This driver requires at least 2 sockets:

  • 1x driver “BlkDrvTcp” on port 11740
  • 1x listen on port 11740 if PLC has established online connection

Note

Online access can be established from:

  • Automation_BuilderCommand ‘Login’: Menu ‘Online’
  • IEC 61131-3 editor OPC DA server
  • Panel CP600 series

Each established connection needs one socket. In addition one socket on port 11740 is listening.

  1. Startup the PLC.

    One socket on port 11740 (listen).

  2. Login from Automation_Builder via driver “BlKDrvTcp”.

    2 sockets on port 11740 (1x online, 1x listen)

  3. Additional login out of OPC server with the same driver.

    3 sockets on port 11740 (2x online, 1x listen)

  4. Additional connect CP600 via driver “BlkDrvTcp”.

    4 sockets on port 11740 (3x online, 1x listen)