Effects and Causes¶
PLC - Device object displays red symbol
It is imperative that you check the Controller status in the Status tab of the device.
Causes
- IP or station name of the controller are doubled
- Driver does not have a license
- Internal error
See also
PLC - Device scan failed
In order for the scan dialog to show the PROFINET devices currently located in the PROFINET network, the data is read in two stages:
- Then all devices are recorded in the PROFINET RT protocol.
- In UDP/IP, the module configuration is read for each device.
Possible problems:
Effect | Cause |
---|---|
PROFINET devices are displayed in the scan dialog, but not the modules of the devices. | The PROFINET device does not have an IP address, or it is located in another subnet than the controller and therefore it is unreachable via UDP. The firewall is configured incorrectly. Another clue for this are error messages in the Log of the PLC. |
Scan dialog displays nothing. | The driver is not started, and the application is stopped. No PROFINET RT packets can be received. |
See also
PROFINET slave device keeps red symbol
The controller is started and it is green (after about 3 sec.), but…
Effect | Cause / Background | ||
---|---|---|---|
…all configured PROFINET slaves remain red. | No connection to the network. Issues with firewall. Check that the device scan functions correctly. |
||
…a PROFINET slave remains red. | Device not in network. Check that the station name is correct. Slave terminates the connection with errors. Performance problems; the communication watchdog starts when establishing the connection. |
||
…PROFINET slaves switch between green, red, and orange. | When establishing the connection, the symbol of the slave is an oranges triangle. The station status is If the In the red/error state, the station status shows the causes. Typical errors are the causes are: |
||
Status: | Cause | ||
81813F02 | DNS unknown RealStationName | Incorrect station name device cannot be reached over the network (see 1.3.1.2) | |
CF81FD05 | Connection aborted: AR consumer DHT expired | Transmit clock cannot be maintained (see 1.4, 1.3.3) | |
CF81FD06 | AR cmi timeout | Transmit clock cannot be maintained (see 1.4, 1.3.3) | |
… PROFINET slave is green, but it has a red exclamation mark, or individual modules are red. | The controller has an active connection, and therefore everything is okay. The PROFINET device reports PROFINET diagnostic messages only for individual modules. |