Differences HA-Modbus TCP (V2/ V3) and HA-CS31

The following table gives an overview of the different High Availability variants possible with AC500.

The figures are indicative, depend on chosen architectures, system size, network and CPU/CM modules used.

Overview of AC500 HA systems \
Library version HA-CS31 HA-Modbus TCP
CPU version V2 CPUs V2 CPUs V3 CPUs
IO Communication Parallel serial ETHERNET ETHERNET
CPUs PM573 - 595 PM573 PM591 PM595 PM5630 PM5650 PM5670
  IO network is based on ETHERNET and external redundancy mechanism
Max. system size IO clusters1, 6) 3 - 50 2) 3 < 25 / 50 < 60 / 92 < 30 < 50 < 100
IO Modules CI590:S500 usable CI52x: S500 and S500-eCo usable 4)
Switch-over times CPU 25 -120 ms 3) ~70 ms 6)
Field 15 - 20 ms Depends mainly on external switches redundancy mechanism: e.g. MRP typ. 150 ms + Modbus cycle time e.g. 40 ms
SCADA connectivity OPC DA, IEC60870, … OPC DA, IEC60870, … OPC DA, OPC UA, IEC60870, …
Programming Codesys V2.3 Codesys V2.3 Codesys V3.5
Interfaces Several CS31 and ETHERNET interfaces Several ETH ports, via CM597 2 Eth ports 5) (+ 1 CAN Interface)
Overview of AC500 HA system alternatives ../_images/929d4d649d8e680b0a317f340465985e ../_images/a126f4fd9d8e69ff0a317f346a49ffad ../_images/b0c7f7f39d8e6b560a317f342b6ba57a

1) Number of I/O clusters recommendation based on performance or max. number of sockets (CPU and CM modules )

2) Limited by CPU performance, number of CM574 modules number of CS31 clients and process data limits.

3) Depends on system size and CPU type

4) Some S500-eCo modules not yet usable, see release notes

5) Communication Module not available

6) see HA-Modbus TCP - System Technology