Input Description¶
SPECIFIER
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
WORD | - | 0-15 | bit |
The bits of the diagnosis specifier describe the type and specification of the current diagnosis:
Bit | Description |
---|---|
0 … 10 | Sequence number |
11 | Channel diagnosis |
12 | Manufacturer specific diagnosis |
13 | Submodule diagnosis state |
14 | Reserved |
15 | AR diagnosis state |
The SPECIFIER can be displayed in plain text using the function PNIO_DEV_SPECIFIER PNIO_DEV_INFO.