RCOM_READ_SLVΒΆ
Parameter | Value |
---|---|
Library_File_Name | RCOM_AC500_V13.lib |
Firmware | V1.3.1 |
Type | Type_Function_Block_History |
Group | RCOM/RCOM+ communication |
This Function Block provides the data to be read by the master using an RCOM_READ Function Block.
The data are provided to the Communication Module with an incoming READ job for the specified flag area.
If EN = FALSE or if the slave has not been normalized before, the function Function Block rejects reading jobs (answer: ‘application part not ready’).
The data record number must match the number in the RCOM_READ function Function Block.
The sender of the reading job is specified at input NODE. Because only the master of an RCOM network can send reading jobs, input NODE always has to be zero.