PROFINET Status*
The PROFINET status of read / write service is described in the following structures:
| ErrorCode |
| 16#DE |
PNIO READ Response |
| 16#DF |
PNIO WRITE Respone |
| ErrorDecode |
| 16#80 |
PNIO READ / WRITE Service |
| ErrorClass |
| 16#0 - 16#9 |
Not Specified / Reserved |
| 16#A |
Application |
| 16#B |
Access |
| 16#C |
Resource |
| 16#D - 16#F |
User / Module specific |
| ErrorCode inside ErrorCode1 for ErrorClass 16#A (Application) |
| 16#0 |
Read error |
| 16#1 |
Write error |
| 16#2 |
Module failure |
| 16#3 - 16#6 |
Not specific / Reserved |
| 16#7 |
Module busy |
| 16#8 |
Version conflict |
| 16#9 |
Feature not supported |
| 16#A - 16#F |
User / Module specific |
| ErrorCode inside ErrorCode1 for ErrorClass 16#B (Access) |
| 16#0 |
Invalid Index |
| 16#1 |
Write lenhth error |
| 16#2 |
Invalid slot / subslot |
| 16#3 |
Type conflict |
| 16#4 |
Invalid area / API |
| 16#5 |
State conflict |
| 16#6 |
Access denied |
| 16#7 |
Invalid range |
| 16#8 |
Invalid parameter |
| 16#9 |
Invalid type |
| 16#A |
Backup |
| 16#B - 16#F |
User / Module specific |
| ErrorCode inside ErrorCode1 for ErrorClass 16#C (Resource) |
| 16#0 |
Read constrain confict |
| 16#1 |
Write constrain confict |
| 16#2 |
Resource busy |
| 16#3 |
Resource unavailable |
| 16#4 - 16#7 |
Not specific / Reserved |
| 16#8 - 16#16 |
User / Module specific |
| ErrorCode2 |
| 16#00 - 16#FF |
User / Module specific |
*)This chapter corresponds in substance to the standard PN-AL-protocol_2722.