Input Description

../_images/828593b2e38ae4d80a33139000eba54e1

EN

Data_Type Default_Value Range Unit
BOOL FALSE TRUE/FALSE -

The input EN has to be driven in level triggered mode.

In order to enable the execution of the Function Block the input EN has to be set to value TRUE. It keeps on executing until the input EN is set back to value FALSE.

While it is executed its inputs are continuously evaluated.

SLOT

Data_Type Default_Value Range Unit
BYTE - 1 … 6 -

The SLOT input selects the Communication Module serving the PROFINET IO-Device described by DEV_NAME. Valid values are 1…6, counting from right to left, starting with 1 as the first Communication Module left to the CPU.

For PM595 Processor Modules, internal PROFINET Communication Module with connector ETH3 is slot 5, ETH4 is slot 6.