Output Description¶
DONE BOOL \ (done)
The output variable DONE shows the processing SEND_C_TS_NA_1_ACT of the Function Block. It shows TRUE when the processing ended or an error took place. This variable DONE should be checked together with the variable ERR. If DONE and ERR are set to TRUE then the output ERNO should be checked to see which error occurred.
ERR BOOL \ (error)
ERR shows TRUE if the Function Block was terminated as a consequence of an error, or FALSE if it ended normally.
ERNO
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
WORD | - | 0 … 65535 | - |
At output ERNO the identifier of an occurred error is provided. It is only valid when DONE and ERR is TRUE. (see, error messages): Error Messages of the Function Block Libraries
RDY BOOL \ (ready)
A command was send if the output RDY = TRUE.
SUCCESS BOOL \ (receive \ monitored \ init \ end)
The test sequence finished successful. The matching answer was received within the specified timeout.
OV BOOL \ (overrun)
Overrun was detected if the output OV = TRUE.
The output OV indicates by changing from FALSE to TRUE, that the transmission requests are coming too fast, i.e. the task cycle time is configured as too fast.
The output always has to be considered together with output RDY.
RTSC BOOL
Received test sequence counter, this must match the requested TSC (Input)
RGADU1 BYTE
Received adress must match the requested adress at input.
RGADU2 BYTE
Received adress must match the requested adress at input.
RIAD1 BYTE
Received adress must match the requested adress at input.
RIAD2 BYTE
Received adress must match the requested adress at input.
RIAD3 BYTE
Received adress must match the requested adress at input.