ETHx_OWN_IP_INFOΒΆ

../_images/52b47f8fe38a1e010a33139000eba54e

The Function Block ETHx_OWN_IP_INFO outputs the IP setup of the Communication Module installed at interface specified by input ETH.

Prior to commissioning an ETHERNET interface, it has to be configured using Automation_Builder software. Using the Function Block ETHx_OWN_IP_INFO, information about the IP setup of the device at ETH can be read. If no ETHERNET interface is installed at input ETH, the corresponding error is generated and output at ERR and ERNO.

Available as of PLC runtime system: V2.4
Included in library: Ethernet_AC500_V10.lib
Type Function Block with historical values