Input Description

../_images/5c352caaac6027770a317d317a4f44a1

EN (enable)

Data_Type Default_Value Range Unit
BOOL FALSE - -

In order to enable the function block processing, input EN has to be continuously set to TRUE. The function block is not processed if input EN = FALSE. While input EN is set to TRUE input IN is evaluated and used to update BACnet object property Present_Value.

OBJ_ID (object ident number)

Data_Type Default_Value Range Unit
WORD 0 0…4194302 -

Defines the BACnet object ident number. The object ident number has to be unique within the BACnet network.

OBJ_NAME (object name)

Data_Type Default_Value Range Unit
STRING(40) Empty string - -

Defines the BACnet object name. The object name has to be unique within BACnet network.

POLAR

Data_Type Default_Value Range Unit
BASC_POLAR_ENUM BASC_NORMAL BASC_NORMAL, BASC_REVERSE -

Defines the polarity of the value that is connected to the input IN. Polarity is defined according to BACnet standard Structures and Enumerations.

IN

Data_Type Default_Value Range Unit
BOOL FALSE - -

To be connected to an IEC variable representing a physical input of the Processor Module. The value will be used to update BACnet property Present_Value.