Input DescriptionΒΆ
EN
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BOOL | FALSE | TRUE/FALSE | - |
The input EN has to be driven in edge triggered mode.
The execution of the Function Block is started with a positive edge on the input EN.
In the first call it evaluates its inputs and creates a local copy of them. Afterwards it starts its internal algorithm. It may take several PLC task cycles until it is executed.
Once the execution is completed DONE and its other outputs are set. To start the Function Block again a new positive edge on the input EN has to be applied.
COM
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BYTE | - | - | - |
Input COM specifies the COM port where the MULTI protocol is configured.
IDX
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BYTE | - | - | - |
Input IDX specifies the index of the sub-module that should be used for the MODBUS communication.
ADDR
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BYTE | - | - | - |
Input ADDR specifies the address that should be set for the corresponding MODBUS slave.