DC541_FREQ_OUTΒΆ

../_images/d0e76bebe389d8a90a33139000eba54e1
Parameter Value
Library_File_Name DC541_AC500_V11.lib
Firmware V1.1.3, DC541 firmware: V1.2
Type Type_Function_Block_History
Group Counters

The Function Block DC541_FREQ_OUT is used to output pulses with a fixed frequency on one channel of the device DC541. It is able to output pulses with a frequency between 0.2 and 2.5 kHz. The pulse jitter depends on the cycle time of the DC541. The pulse length is always a multiple of the cycle time of the DC541.

In case of a presetting of PULSE = 0, the output of pulses is infinite. The pulse output is started with a positive edge at input START. The output is aborted if START = FALSE. A positive edge at input STOP interrupts the pulse output. The output is continued if STOP = FALSE.

If input PULSE > 0, the Function Block outputs the number of pulses specified at input PULSE with the frequency specified at input FREQ on the channel specified at input CH. After the Function Block has output the number of pulses specified at PULSE, the output RDY becomes TRUE.

The device DC541 must be configured as counting device (counter mode). Channel CH must be configured for frequency output.

The Function Block has an integrated visualization which can be used to control all Function Block functions in parallel to the user program, if input EN_VISU = TRUE.