PNIO_CNTL_START_COM¶
Available as of PLC runtime system | V2.6.2 and above |
Available as of AB version | V2.1 and above |
Available as of CM579-PNIO version | V2.8.4.20 and above |
Included in library | Profinet_Ext2_AC500_V26.lib |
Type | Function Block with historical values. |
The function block PNIO_CNTL_START_COM can be used to start the communication of the PROFINET IO Controller. That means the communication state is changed from Stop to Operate.
The next figure shows the flowchart of the execution of the Function Block PNIO_CNTL_START_COM.:
When the execution is started the bus communication will be enabled. After that the communication state of the PROFINET IO Controller is checked and it’s waited until the communication state is Operate.
The execution of the FB was successful if the PROFINET IO Controller was changed to the communication state Operate.
If the PROFINET IO Controller is not in the communication state Operate within the specified timeout the execution of the FB is failed and the bus communication is disabled again.