Input DescriptionΒΆ
EN
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BOOL | FALSE | TRUE/FALSE | - |
The input EN has to be driven in edge triggered mode.
The execution of the Function Block is started with a positive edge on the input EN.
In the first call it evaluates its inputs and creates a local copy of them. Afterwards it starts its internal algorithm. It may take several PLC task cycles until it is executed.
Once the execution is completed DONE and its other outputs are set. To start the Function Block again a new positive edge on the input EN has to be applied.
COM
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BYTE | - | - | - |
At input COM, the MODBUS interface number is specified.
COM = 1: COM1
COM = 2: COM2
SLAVE
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BYTE | - | - | - |
At input SLAVE, the address of the slave to which the telegram shall be sent is specified.
FCT
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BYTE | - | - | - |
The function code of the request telegram is specified at input FCT.
01 or 02 | Read n bits |
03 or 04 | Read n words |
05 | Write one bit (encoded in one word) |
06 | Write one word |
07 | Read 8 Bit |
15 | Write n bits (encoded in one byte) |
16 | Write n words |
22 | Mask write |
23 | Read/write multiple words in one telegram |
TIMEOUT
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
WORD | - | - | ms |
The telegram timeout in milliseconds (ms) is specified at input TIMEOUT.
If no response is received within the time interval specified in TIMEOUT, the procedure is aborted and an error identifier is output.
Note
Keeping the timeout depends on the cycle time of the task in which the MODMAST Function Block is processed. The real time may deviate from the specification in worst case by task cycle time - 1 ms.
ADDR
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
WORD | - | - | - |
The operand/register address in the slave from which data should be read or written is specified at input ADDR.
The access to operands of AC500 devices in MODBUS slave mode is defined via the MODBUS cross-reference list. Only operands that are listed in the cross-reference list may be used (Communication with: Communication \ with MODBUS RTU
Only operands that are listed in the MODBUS address list may be used. When accessing other devices, ADDR is freely selectable. The valid ranges have to be gathered from the corresponding device description.
NB WORD \ (number)
At input NB, the number of data to be written or read is specified. The unit of NB depends on the selected function. For bit accesses the number of bits, for word and double word accesses the number of words is specified at NB. The following restrictions apply to the length:
FCT | NBmax | ||
---|---|---|---|
Dec | Hex | Serial | MODBUS on TCP/IP |
01 or 02 | 01 or 02 | 2000 bits | 255 bits (up to firmware version V01.33) 1800 bits (from firmware version V01.41) 1536 bits (PM573/PM583 only) |
03 or 04 | 03 or 04 | 125 words / 62 double words | 125 words / 62 double words |
05 | 05 | 1 bit | 1 bit |
06 | 06 | 1 word | 1 word |
07 | 07 | 8 bits | 8 bits |
15 | 0F | 1968 bits | 255 bits (up to firmware version V01.33) 1800 bits (from firmware version V01.41) 1536 bits (PM573/PM583 only) |
16 | 10 | 123 words / 61 double words | 123 words / 61 double words |
22 | 16 | Write: 1 word | Write: 1 word |
23 | 17 | Read: 125 words / 62 double words Write: 123 words / 61 double words |
Read: 125 words / 62 double words Write: 123 words / 61 double words |
DATA
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
DWORD | - | - | - |
At input DATA, the address of the first operand in the master is specified, from which data are copied/written to the slave or to which the data read by the slave should be stored. For this purpose it is necessary that the operand type (e.g. bit) matches the selected function (e.g. FCT 1, read n bits).
If using MODBUS function codes 22 or 23, the according data structures COM_MOD_FCT22_TYPE COM_MOD_FCT22_TYPE or COM_MOD_FCT23_TYPE COM_MOD_FCT23_TYPE must be defined and applied to DATA.