IEC60870_DISABLE

../_images/45921b41568155cd0a317f340cec4f43

The function block IEC60870_DISABLE can be used to shut down all IEC60870 connections on a PLC.

No further connections can be established after the function block IEC60870_DISABLE has been executed with EN=TRUE and ACTIVE=FALSE.

All already established connections will be aborted. The PLC won’t answer any IEC60870-5-104 connections request any more.

When the IEC60870_DISABLE function block gets executed with EN=TRUE and ACTIVE=TRUE the PLC will listen for new IEC60870-5-104 connections again, and also try to establish connections again.

Parameter Value
Library_File_Name IEC60870_AC500_V20.lib
Firmware V2.6.2 and above
Type Type_Function_Block_History
Group Data