BASC_BINARY_VAL¶
Parameter | Value |
---|---|
Library_File_Name | BACnet_B-ASC_AC500_V25.lib |
Firmware | V2.5 |
Type | Type_Function_Block_History |
Group | C interface |
BASC_BINARY_VAL allows to connect an IEC variable with a BACnet object type “binary value”. This object represents a binary value that is neither physical input nor physical output of the device. Connect the internal IEC variables to this function block only.
Property name | Characteristics | Value | BACNet conformance code |
---|---|---|---|
Object_Identifier | Set via input OBJ_ID | - | R - read |
Object_Name | Set via input OBJ_NAME | - | R - read |
Present_Value | Set via input VALUE Updates output VALUE |
- | W – read/write |
Status_Flags | Updates output STATUS_FLAG | - | R - read |
Object_Type | Constant | BINARY_VALUE (5) | R - read |
Event_State | Constant | NORMAL (0) | R - read |
Out_Of_Service | Set via BACnet write services | - | W - read/write |
Priority_Array | Set via BACnet write services | - | R - read |
Relinquish_Default | Constant | INACTIVE | R - read |