Input Description

../_images/ce20ab8323c2790c0a317f344e01d70b

EN

Data_Type Default_Value Range Unit
BOOL FALSE TRUE/FALSE -

The input EN has to be driven in level triggered mode.

In order to enable the execution of the Function Block the input EN has to be set to value TRUE. It keeps on executing until the input EN is set back to value FALSE.

While it is executed its inputs are continuously evaluated.

SLOT

Data_Type Default_Value Range Unit
BYTE 0 0 … 4 (6) -

At input SLOT, the Communication Module slot is specified which should be used by the Function Block.

The internal Communication Module always has the index 0. All external Communication Modules are serially numbered from right to left, starting with 1.

PULSE_WIDTH

Data_Type Default_Value Range Unit
WORD - 40 … 32767 µs

The input PULSE_WIDTH gives the time in microseconds which is used to increase the internal counter by 1. Also, this gives the minimal time available for switching on a binary output. All other times are a multiple of this time

PERIOD

Data_Type Default_Value Range Unit
WORD - 2 … 255 PULSE_WIDTH length

Period duration [in number of pulses], i.e. internal counter value is being set to 0 when this value is reached.

ON_DUR

Data_Type Default_Value Range Unit
WORD - - -

Duration [in number of pulses] for switching on the respective binary output.