Recommended Use of ETHERNET ConnectionsΒΆ

The following types of ETHERNET communication is required:

  • UDP: Communication between the two CPUs for HA synchronization.
  • AB: Communication between CPUs and Engineering PC for program download.
  • OPC: Communication between CPUs and HMI (optionally).
  • WEB: Web server communication between CPUs and HMI (optionally).

ETHERNET ports are available on the CPU (onboard) and on the CM577-ETH communication module. For an optimal load balance the following connections are recommended:

CPU Type Web server required Onboard ETH1 Onboard ETH2 CM577-ETH
PM57x, PM58x, PM591, PM592 No UDP n/a AB, OPC
PM57x, PM58x, PM591, PM592 Yes AB, OPC, WEB n/a UPD
PM592-2ETH, PM595 No UDP AB, OPC -
PM592-2ETH, PM595 Yes UDP AB, OPC, WEB -

Note

PM591-2 ETH and PM595 PLCs must use onboard ETH1 for UDP data communication.