Output Description¶
DONE
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BOOL | - | TRUE / FALSE | - |
Output DONE indicates the state of execution.
It has the value TRUE when the execution is finished and the outputs are valid. When DONE becomes FALSE other outputs are not valid any more.
ERR
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BOOL | - | TRUE / FALSE | - |
Output ERR indicates whether an error occurred during Function Block execution.
It is only valid when DONE is TRUE. The kind of occurred error is specified by the error identifier at output ERNO.
ERNO
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
WORD | - | 0 … 65535 | - |
At output ERNO the identifier of an occurred error is provided. It is only valid when DONE and ERR is TRUE (see, error messages): Error Messages of the Function Block Libraries
NODE_ID
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BYTE | - | - | - |
Output NODE_ID displays the own NODE ID of the Communication Module.
LEN
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
WORD | - | - | byte |
Output LEN displays the length of the received data package in bytes.
LEV_DS
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
WORD | - | - | - |
Output LEV_DS displays the filling level of the receive buffer in data records. The displayed value is updated as long as EN is TRUE and applies to the input values read with the rising edge at input EN.