BASC_ANALOG_VAL

../_images/0f03b242ac59a52d0a317d3140b0dc1a
Parameter Value
Library_File_Name BACnet_B-ASC_AC500_V25.lib
Firmware V2.5
Type Type_Function_Block_History
Group C interface

BASC_ANALOG_VAL allows to connect an IEC variable with a BACnet object type “analog value”. This object represents an analog value that is neither physical input nor physical output of the device. Connect the internal IEC variables to this function block only.

Analog value object properties provided at the BACnet network by BASC_ANALOG_VAL
Property Characteristics Value BACNet conformance code
Object_Identifier Set via input OBJ_ID - R - read
Object_Name Set via input OBJ_NAME - R - read
Units Set via input UNIT - R - read
Present_Value Set via input VALUE, Updates output VALUE - W – read/write
Status_Flags Updates output STATUS_FLAG - R - read
Object_Type Constant ANALOG_VALUE (2) R - read
Event_State Constant NORMAL (0) R - read
Out_Of_Service Set via BACnet write services - W - read/write
Priority_Array Set via BACnet write services - R - read
Relinquish_Default Constant 0.0 R - read