BASC_ANALOG_OUT

../_images/492e730fac4c73cc0a317d317639e5b3
Parameter Value
Library_File_Name BACnet_B-ASC_AC500_V25.lib
Firmware V2.5
Type Type_Function_Block_History
Group C interface

BASC_ANALOG_OUT allows to connect an IEC variable with a BACnet object type “analog output”. This object represents a physical analog output of the device. Connect the variables mapped to the physical analog outputs to this function block only.

Analog output object properties provided at the BACnet network by BASC_ANALOG_OUT
Property Characteristics Value BACNet conformance code
Object_Identifier Set via input OBJ_ID - R - read
Object_Name Set via input OBJ_NAME - R - read
Units Set via input UNIT - R - read
Present_Value Updates output OUT - W - read/write
Status_Flags Updates output STATUS_FLAG - R - read
Object_Type Constant ANALOG_OUTPUT (1) R - read
Event_State Constant NORMAL (0) R - read
Out_Of_Service Set via BACnet write services - W - read/write
Priority_Array Set via BACnet write services - R - read
Relinquish_Default Constant 0.0 R - read