Output Description

../_images/04e6ff80fe5ec12a0a33139001ad0809

Function block HA_CS31_DIAG_EXTD

DONE

Data_Type Default_Value Range Unit
BOOL - TRUE / FALSE -

Output DONE indicates the state of execution.

It has the value TRUE when the execution is finished and the outputs are valid. When DONE becomes FALSE other outputs are not valid any more.

ERR

Data_Type Default_Value Range Unit
BOOL - TRUE / FALSE -

Output ERR indicates whether an error occurred during Function Block execution.

It is only valid when DONE is TRUE. The kind of occurred error is specified by the error identifier at output ERNO.

ERNO

Data_Type Default_Value Range Unit
WORD - 0 … 65535 -

At output ERNO the identifier of an occurred error is provided. It is only valid when DONE and ERR is TRUE. (see, error messages): Error Messages of the Function Block Libraries

BOOL_OUT_EQ (bool out equality)

Data type: DWORD.

Each bit of this DWORD represents a CI590-CS31-HA with identical buffer for digital type.

BOOL_OUT_DIFF (bool out difference)

Data type: BOOL.

Error bit to indicate that the output buffer for digital type data is different in one or more CI590-CS31-HA which are active on the Bus.

ANALOG_OUT_EQ (analog out equality)

Data type: DWORD.

Each bit of this DWORD represents a CI590-CS31-HA with identical buffer for analog type.

ANALOG_OUT_DIFF (analog out difference)

Data type: BOOL.

Error bit to indicate that the output buffer for analog type data is different in one or more CI590-CS31-HA which are active on the Bus.