Input Description¶
EN
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BOOL | FALSE | TRUE/FALSE | - |
The input EN has to be driven in level triggered mode.
In order to enable the execution of the Function Block the input EN has to be set to value TRUE. It keeps on executing until the input EN is set back to value FALSE.
While it is executed its inputs are continuously evaluated.
SYNC_SLOT
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BYTE | 3 | 1 … 3 | - |
Slot number on which Sync Communication is configured.
SEC_SLOT
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BYTE | 2 | 1 … 3 | - |
Slot number on which second communication LifeCom2 is configured.
IP_ADR_CPU_A_SYNC
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
STRING(16) | ‘0.0.0.0’ | - | - |
IP Address (on which SYNC Communication is configured) of AC500 CPU connected to PLC A.
IP_ADR_CPU_B_SYNC
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
STRING(16) | ‘0.0.0.0’ | - | - |
IP Address(on which SYNC Communication is configured) of AC500 CPU connected to PLC B.
IP_ADR_CPU_A_LIFECOM2
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
STRING(16) | ‘0.0.0.0’ | - | - |
IP Address(on which LifeCom2 Communication is configured) of AC500 CPU connected to PLC A.
IP_ADR_CPU_B_LIFECOM2
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
STRING(16) | ‘0.0.0.0’ | - | - |
IP Address(on which LifeCom2 Communication is configured) of AC500 CPU connected to PLC B.
MANUAL_CHG_OVER
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BOOL | FALSE | - | - |
TRUE- Manual changeover from primary to secondary PLC.
SUPER_CHG_OVER
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BOOL | FALSE | - | - |
TRUE- Suppress changeover (from primary to secondary PLC)
Prepared for future use (If used this input should be activated in both the CPU at the same time else system may behave randomly.
Note
Suppress changeover feature is recommended to use only during network reconfiguration and not during any other switchover scenarios for example PLC STOP Output: