Input Description

../_images/d5ab5e709dd89bb90a317f342dc896891

EN

Data_Type Default_Value Range Unit
BOOL FALSE TRUE/FALSE -

The input EN has to be driven in level triggered mode.

In order to enable the execution of the Function Block the input EN has to be set to value TRUE. It keeps on executing until the input EN is set back to value FALSE.

While it is executed its inputs are continuously evaluated.

SYNC_SLOT

Data_Type Default_Value Range Unit
BYTE 3 1 … 3 -

Slot number on which Sync Communication is configured.

SEC_SLOT

Data_Type Default_Value Range Unit
BYTE 2 1 … 3 -

Slot number on which second communication LifeCom2 is configured.

IP_ADR_CPU_A_SYNC

Data_Type Default_Value Range Unit
STRING(16) ‘0.0.0.0’ - -

IP Address (on which SYNC Communication is configured) of AC500 CPU connected to PLC A.

IP_ADR_CPU_B_SYNC

Data_Type Default_Value Range Unit
STRING(16) ‘0.0.0.0’ - -

IP Address(on which SYNC Communication is configured) of AC500 CPU connected to PLC B.

IP_ADR_CPU_A_LIFECOM2

Data_Type Default_Value Range Unit
STRING(16) ‘0.0.0.0’ - -

IP Address(on which LifeCom2 Communication is configured) of AC500 CPU connected to PLC A.

IP_ADR_CPU_B_LIFECOM2

Data_Type Default_Value Range Unit
STRING(16) ‘0.0.0.0’ - -

IP Address(on which LifeCom2 Communication is configured) of AC500 CPU connected to PLC B.

MANUAL_CHG_OVER

Data_Type Default_Value Range Unit
BOOL FALSE - -

TRUE- Manual changeover from primary to secondary PLC.

SUPER_CHG_OVER

Data_Type Default_Value Range Unit
BOOL FALSE - -

TRUE- Suppress changeover (from primary to secondary PLC)

Prepared for future use (If used this input should be activated in both the CPU at the same time else system may behave randomly.

Note

Suppress changeover feature is recommended to use only during network reconfiguration and not during any other switchover scenarios for example PLC STOP Output: