Input Description

../_images/6ac7d806e38af2310a33139000eba54e1

EN

Data_Type Default_Value Range Unit
BOOL FALSE TRUE/FALSE -

The input EN has to be driven in edge triggered mode.

The execution of the Function Block is started with a positive edge on the input EN.

In the first call it evaluates its inputs and creates a local copy of them. Afterwards it starts its internal algorithm. It may take several PLC task cycles until it is executed.

Once the execution is completed DONE and its other outputs are set. To start the Function Block again a new positive edge on the input EN has to be applied.

SLOT

Data_Type Default_Value Range Unit
BYTE 0 0 … 4 (6) -

At input SLOT, the Communication Module slot is specified which should be used by the Function Block.

The internal Communication Module always has the index 0. All external Communication Modules are serially numbered from right to left, starting with 1.

NODE

Data_Type Default_Value Range Unit
WORD - - -

Input NODE specifies the number of the slave. The value 255 sets all slaves to the same time (all slaves are called).

HOUR_SET

Data_Type Default_Value Range Unit
WORD - - -

Input HOUR_SET specifies the value of the hour component of the time.

MIN_SET

Data_Type Default_Value Range Unit
WORD - - -

Input MIN_SET specifies the value of the minutes component of the time.

SEC_SET

Data_Type Default_Value Range Unit
WORD - - -

Input SEC_SET specifies the value of the seconds component of the time.