Input Description

../_images/d1fa788dfe5ef0e30a33139000953a9b

Function block HA_CS31_DIAG_VIA-CM574

EN (enable)

Data_Type Default_Value Range Unit
BOOL - - -

In order to enable the function block processing, input EN has to be continuously set to TRUE. The function block is not processed if input EN = FALSE. While input is set to TRUE, the inputs are continuously checked for validity and plausibility. If this is not the case, processing is aborted and an error is displayed.

SLOT

Data_Type Default_Value Range Unit
BYTE 0 0 … 4 (6) -

At input SLOT, the Communication Module slot is specified which should be used by the Function Block.

The internal Communication Module always has the index 0. All external Communication Modules are serially numbered from right to left, starting with 1.

COM

Data type: BYTE, default value: 1, range: 1 to 2.

Communication port number of the CS31 master.