TECT_PROCESS_SET_TYPEΒΆ

This structure contains process set parameters of the zone data. User can define all parameters which are related to the process, i.e. parameters which are set as per process properties. These parameters will be changing continuously as per process requirement, e.g. Control word.

PID setpoint, control word, high and low temp settings come under this structure.

No Name Data Type Unit Initial Value Description Access
1 wControlWord WORD   0 Control word RW
  enable: BOOL     Bit 0: enable Process.  
  heat_en: BOOL    

Bit 1: enable zone as heat zone.

If both heat_en and cool_en are FALSE then zone is monitor only

 
  cool_en: BOOL    

Bit 2: enable zone as cooling zone.

If both heat_en and cool_en are FALSE then zone is monitored only

 
  manual_en: BOOL     Bit 3: manual mode - highest priority mode, disable all other modes.  
  standby_en: BOOL     Bit 4: standby setpoint is used.  
  tune_en: BOOL     Bit 5: enable auto tune with large setpoint step.  
  accept_auto_tune: BOOL     Bit 6: accept or reject tuning parameters.  
  co_output: BOOL     Bit 7: coordinated output of one group.  
  Reserved BOOL     Bit 8: Reserved  
  Control_Optimization: BOOL    

Bit 10, Bit 9:

- 00: APERIODIC,

- 01: OVERSHOOT,

- 10: DEADTIME COMPENSATION,

- 11: NO OPTIMIZATION .

 
  warm_reset: BOOL     Bit 13: reset the alarm and process but not AutoTune status.  
  en_3phase_Monitor BOOL     Bit 14 - True :3phase current monitoring False: single phase monitoring  
  cold_reset: BOOL     Bit 15: reset all in control process.  
2 iManual_Duty_Cycle INT   0 PWM output in manual mode. RW
3 rSetPoint REAL   0 Process setpoint. RW
4 rStandBy_SetPoint REAL   0 Secondary process setpoint for standby. RW
5 rHigh_Temp REAL   32767 High temperature alarm, disables heat output. RW
6 rLow_Temp REAL   - 32767 Low temperature alarm, disables cool output. RW
7 rHigh_Deviation REAL   0 High deviation alarm, relative to setpoint. RW
8 rLow_Deviation REAL   0 Low deviation alarm, relative to setpoint. RW